Three-Phase Power Calculator

Compute real power delivered by a balanced three-phase supply.

Formula

P = √3 × VL × IL × PF

Inputs

What it does

Real power delivered by a balanced three-phase supply: P = √3 × V_L × I_L × PF.

Where it's used

Motors, industrial loads and sizing three-phase supplies.

How to use it

  1. Enter the line-to-line voltage.
  2. Enter the line current.
  3. Enter the power factor (from the nameplate or a meter).

The formula explained

V_L
line-to-line voltage
I_L
line current
PF
power factor (cos φ)
√3
about 1.732, from the 120° phase spacing

Worked example

Inputs:

The calculator gives:

Tips and common mistakes

Questions people ask

How do I find the current from the power?

I = P / (√3 × V_L × PF). An 11 kW motor on 415 V with a power factor of 0.85 draws about 18 A per line.

What is the difference between line and phase voltage?

Line voltage is measured between two phases; phase voltage between a phase and neutral. In a star system V_L = √3 × V_ph, so 230 V phase voltage gives about 400 V between lines.

Why is three-phase used for big loads?

It delivers power smoothly instead of in pulses, needs less copper than single-phase for the same power, and gives motors a rotating magnetic field so they start and run without extra parts.