AC Power Calculator
Real, reactive and apparent power for 1-phase or 3-phase loads, plus PF-correction capacitor.
What it does
AC loads such as motors draw current that is out of step with the voltage. That splits power into real (W), reactive (var) and apparent (VA). The calculator also finds the capacitor needed to improve the power factor.
Where it's used
Motors and pumps, sizing generators and UPS units (rated in VA), and power-factor correction.
How to use it
- Choose single- or three-phase.
- Enter voltage (line-to-line for three-phase), current and power factor.
- Enter the supply frequency.
- Enter a target power factor to size the correction capacitor.
The formula explained
- S
- apparent power, VA — what cables and UPS units must carry
- P
- real power, W — what does useful work and is billed
- Q
- reactive power, var — circulates back and forth
- cos φ
- power factor = P / S
- C
- capacitor that cancels the extra reactive power
Worked example
A three-phase motor at 415 V drawing 25 A with a power factor of 0.75.
Inputs:
- System: Three-phase (line-to-line V)
- Voltage (RMS): 415 V
- Current (RMS): 25 A
- Power factor cos φ: 0.75
- Supply frequency: 50 Hz
- Target power factor: 0.95
The calculator gives:
- Real power P: 13.48 kW
- Apparent power S: 17.97 kVA
- Reactive power Q: 11.89 kvar
Tips and common mistakes
- UPS and generator ratings are in VA (S), not W.
- Use the line-to-line voltage for three-phase systems.
- Correcting much beyond about 0.95–0.98 gives little benefit and risks a leading power factor.
Questions people ask
What does the power factor mean?
Power factor is real power divided by apparent power, P / S = cos φ. At 0.75 only 75 % of the current drawn does useful work; the rest flows back and forth to build the motor’s magnetic field.
How is the correction capacitor sized?
The capacitors must supply Q_c = P × (tan φ1 − tan φ2) of reactive power. For the example motor (13.48 kW, from 0.75 to 0.95) that is about 7.46 kvar, which the calculator turns into microfarads per phase.
Why does a low power factor cost money?
For the same real power, a low power factor means more current, so cables, transformers and switchgear must be bigger and losses are higher. Many electricity tariffs for businesses charge extra when the power factor falls below about 0.9.
Related Power & Circuits calculators
- DC Power Calculator
- Buck Converter Calculator
- Boost Converter Calculator
- 555 Timer — Astable
- 555 Timer — Monostable
- Inverting Op-Amp Gain
- Non-Inverting Op-Amp Gain
- Op-Amp Voltage-to-Current Converter
- Electrical Power
- Voltage Drop
- Three-Phase Power
- Electrical Energy
Enter your values to get the result with the formula, substituted values and an explanation of each step.