Op-Amp Voltage-to-Current Converter Calculator

Output current, load compliance and sense resistor for a V-to-I (transconductance) stage, e.g. 4–20 mA.

What it does

A voltage-to-current converter forces a current set by the sense resistor through the load: I = Vin / Rsense, as long as the op-amp can supply enough voltage (compliance).

Where it's used

Driving 4–20 mA industrial current loops and constant-current sources.

How to use it

  1. Choose whether to find the current or the sense resistor.
  2. Enter the control voltage and Rsense (or the full-scale current).
  3. Enter the load resistance and the supply.
  4. Check that the compliance result is within the output swing.

The formula explained

I
Vin / Rsense — load current
Rsense
resistor that sets the current
Compliance
I × (R_L + Rsense) must stay below the output swing

Worked example

A 20 mA full-scale loop from a 2.5 V control signal into 500 Ω.

Inputs:

The calculator gives:

Tips and common mistakes

Questions people ask

How is the sense resistor chosen?

R_sense = V_in(max) / I(full scale). A 2.5 V control signal for 20 mA needs 125 Ω, which dissipates 50 mW at full scale.

What is compliance voltage?

The voltage the op-amp must produce to push the current through the load and sense resistor: 20 mA × (500 Ω + 125 Ω) = 12.5 V in the example. Add the op-amp’s own headroom; if the supply can’t provide that, the current falls short.

Why do current loops use 4–20 mA instead of 0–20 mA?

The “live zero” at 4 mA lets the receiver tell a reading of zero from a broken wire (0 mA), and leaves enough current to power a two-wire transmitter from the loop itself.