Power
Power is the rate of energy transfer. Master P = VI and its Ohm's-law forms, efficiency, power ratings, circuit loading and an introduction to AC real, reactive and apparent power.
Power tells you how fast energy is being converted: a 2 kW kettle turns electrical energy into heat twice as fast as a 1 kW one. It is the number on every appliance label and the quantity that decides wire sizes, breaker ratings, heat-sink sizes and battery life.
In DC circuits power is simply voltage times current. In AC circuits the voltage and current can be out of step, which splits power into real, reactive and apparent parts — an idea that runs through the whole of power engineering.
An analogy
A waterfall's power depends on both its height (voltage) and how much water goes over per second (current). A tall trickle and a short torrent can deliver the same power.
Power = voltage × current
Each coulomb delivers V joules, and I coulombs arrive per second, so energy arrives at V·I joules per second — watts. Combine with Ohm's law (V = IR) to get the two other forms: I²R (useful when you know the current, e.g. cable losses) and V²/R (useful when you know the voltage, e.g. a heater on mains).
Power ratings
Every component has a maximum power it can dissipate. A 0.25 W resistor asked to dissipate 0.5 W will overheat. The standard practice is to derate: choose a part rated at least 2× the expected dissipation.
Efficiency and losses
No conversion is perfect. Losses (heat) = P_in − P_out. A 90 %-efficient 500 W power supply draws 556 W and must get rid of 56 W as heat. Efficiency compounds: two 95 % stages in series give 0.95² = 90.25 %.
AC power: real, reactive and apparent
With inductive or capacitive loads the current is shifted in time from the voltage by an angle φ. Only the in-phase part of the current does useful work (real power P, watts). The out-of-phase part sloshes energy back and forth (reactive power Q, vars). Their vector sum is apparent power S = V·I (VA), which is what cables and transformers must be sized for.
Power factor pf = P/S = cos φ. A motor running at pf = 0.7 draws 43 % more current than it would at pf = 1 for the same useful power.
Instantaneous power and non-sinusoidal loads
p(t) = v(t)·i(t). For sinusoids it pulses at twice the line frequency around its average P. Rectifier-fed loads draw distorted, spiky current, so their power factor has a displacement part (cos φ) and a distortion part; true pf = P / (V_rms·I_rms) accounts for both. Standards such as IEC 61000-3-2 limit harmonic current, which is why power supplies above 75 W include active power-factor correction (PFC).
Formulas
- DC power:
P = V · I = I² · R = V² / R - Efficiency:
η = P_out / P_in × 100 % - AC power:
P = V_rms · I_rms · cos φ - Power triangle:
S² = P² + Q², S = V_rms · I_rms
Worked example: Kettle on the mains
Given: P = 2.2 kW; V = 230 V (resistive load)
Find: Current drawn and element resistance.
- I = P / V = 2200 / 230 = 9.57 A
- R = V² / P = 230² / 2200 = 24.0 Ω
- Check: I²R = 9.57² × 24.0 ≈ 2200 W ✓
Answer: I ≈ 9.6 A, R ≈ 24 Ω
Worked example: Motor at low power factor
Given: P = 7.5 kW; V = 400 V single-phase equivalent; pf = 0.75
Find: Apparent power, current and reactive power.
- S = P / pf = 7.5 / 0.75 = 10 kVA
- I = S / V = 10 000 / 400 = 25 A
- Q = √(S² − P²) = √(100 − 56.25) = 6.61 kvar
Answer: S = 10 kVA, I = 25 A, Q ≈ 6.6 kvar
Common mistakes
- Wrong: Using P = V × I with peak AC values. — Right: Use RMS values and include the power factor: P = V_rms · I_rms · cos φ.
- Wrong: Choosing a resistor rated exactly at its calculated dissipation. — Right: Derate — pick at least twice the calculated power, more in hot enclosures.
Applications
- Circuit breakers: Adding up appliance powers on one circuit and dividing by the voltage tells you whether a 16 A or 32 A breaker will trip.
- Thermal design: Every watt dissipated in a MOSFET or regulator must leave through a heat sink; power loss sets the heat-sink size.
- Utility tariffs: Industrial customers pay penalties for low power factor, so they install capacitor banks to cancel reactive power.
Key takeaways
- P = VI = I²R = V²/R for DC and resistive loads.
- Efficiency = P_out/P_in; losses become heat that must be removed.
- In AC, only the in-phase current does work: P = V·I·cos φ.
- Cables and transformers are sized for apparent power (VA), not watts.
Going further
- Maximum power vs maximum efficiency: Delivering maximum power to a load requires matching it to the source resistance, which caps efficiency at 50 %. Power systems do the opposite — source impedance is tiny compared with the load — to maximise efficiency.
- Power measurement in three-phase systems: The two-wattmeter method measures total power in a three-wire system with two meters; their difference also reveals the power factor. Modern energy meters sample v and i digitally and compute P, Q, S and harmonics directly.
- Power density limits: Converters are judged by W/cm³. Wide-bandgap devices (GaN, SiC) switch faster with lower losses, allowing higher frequencies, smaller magnetics and chargers a fraction of the size of silicon designs.